Insights

Short reads on the charges that cost buildings the most, and what to do about them.

What is a demand charge, and why is it so big?

A larger building's ComEd bill charges for two different things. One is energy: how many kilowatt-hours the building used over the month. The other is demand: the most power the building drew at once, measured in kilowatts over a single half hour. For many larger accounts, ComEd measures demand on weekdays between 9 am and 6 pm.

That one half hour sets the demand charge for the whole month. In a middle school we reviewed, demand charges came to $26,424 of a $64,323 electric bill: 41 cents of every dollar, at about $13 per kilowatt. The school wasn't using too much electricity. In fact it used less per square foot than most similar schools. It was using it all at once.

The usual cause is the morning start-up. Rooftop units, air handlers and kitchen equipment all switch on together, and that spike becomes the month's peak.

What to do: look at the building's half-hour meter data to see which half hours set the peak. Then stagger the start-up so equipment comes on in steps, and finish pre-cooling or pre-heating before the demand window opens. ComEd's efficiency programs can help pay for a study to tune the controls.

Why your capacity charge resets every June

Somewhere on your electric supply bill is a capacity charge. It pays for the regional grid, run by PJM Interconnection, to have enough power plants ready for the hottest hours of the year. Depending on your supply contract, it shows up as its own line or is built into your price.

Your share is set by your building's own draw during the five highest-demand hours on the regional grid the summer before. That share takes effect on June 1 and stays for twelve months. The price comes from PJM's capacity auction, and it jumped in June 2025, from $28.92 to $269.92 per megawatt-day.

For the middle school above, the capacity charge came to $8,549 a year, set by what the building was doing on a handful of hot summer afternoons.

What to do: keep load down on the hottest summer weekday afternoons, when the grid's peak hours land. Half-hour meter data shows your draw during last summer's peak hours, so you can see next June's number coming and budget for it before the bill arrives.

Is your empty school running a school-day schedule all summer?

In one middle school we reviewed, the building ran a full school-day schedule on 44 of 46 summer weekdays. It started up at 6 am to about 159 kilowatts and ran near 118 kilowatts until 3 pm, more than a normal school day, while most of the building sat empty. That was worth about $1,385 a year.

Nights and weekends were the lowest of the year, so the controls worked. The weekday schedule simply never changed for the break. It's common: summer programs use one wing, so the whole building stays on. Classroom units that aren't on the building automation system often keep running too.

How to check: compare a July weekday with a school-year weekday in your half-hour meter data. ComEd lets you download it free from your online account.

What to do: set a summer weekday schedule that runs only the occupied wing, starts later and ends earlier, and confirm which weeks actually had programs. Schedule classroom units from their central controller rather than room by room.

Want to know what your own bills show? Request a BLOCK Assessment or see a real example.